Title :
Application of single-pole auto reclosing of circuit breakers in EHV transmission line with capacitance grounding
Author :
Basu, K.P. ; Hamid, S. ; Hasan, Sumbul
Author_Institution :
Fac. of Eng., Multimedia Univ., Malaysia
Abstract :
Tripping of one pole of circuit breakers at both ends of a transmission line for clearing LG fault produces high negative sequence current in nearby generators. Insertion of grounding capacitor connected between the ground and neutral point of star winding of a transformer at one end of the transmission line during the period of open conductor makes the net zero sequence reactance to be zero. The zero sequence network shunts the negative sequence network and the negative sequence current is reduced to a negligible value. The power transfer with one phase open, during single pole auto reclosing becomes equal to pre-fault power and the transient stability limit is highly improved. Power swing associated with a successful auto reclosure becomes minimum. The sudden change in generator output power at the instant of reclosing is reduced to a minimum.
Keywords :
circuit breakers; earthing; power capacitors; power transformers; power transmission faults; power transmission lines; power transmission protection; transformer windings; EHV transmission line; capacitance grounding; circuit breakers; generators; negative sequence current; net zero sequence reactance; output power changes; power transfer; pre-fault power; single phase to ground fault clearing; single-pole auto reclosing; transformer star winding; transient stability limit; Capacitance; Capacitors; Circuit breakers; Circuit faults; Conductors; Distributed parameter circuits; Grounding; Power generation; Power system transients; Power transmission lines;
Conference_Titel :
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN :
0-7803-7525-4
DOI :
10.1109/TDC.2002.1177722