Title :
A new technique to diagnose the oil-filled transformers based on the condensing analysis for very small decomposed products in insulating oil
Author :
Ishii, Tadashi ; Oshi, Tetsuo ; Makino, Yoshihiro ; Hara, Takashi
Author_Institution :
Tokyo Electr. Power Co. Inc., Japan
Abstract :
Analysis of gases dissolved in insulating oil offers the most important and efficient diagnostic method to detect the faults in oil-filled transformers. We carried out a survey of decomposed products from various kind of solid-materials through simplified model tests and current using model tests. The gas chromatography-mass spectrometer and the purge/trap gas extraction equipment are employed to condense and analyze very small decomposed products. As a result, we found out effective decomposed products for diagnosis. This paper describes the new technique for diagnosis based on the decomposed products utilizing the condensing analysis with a view to early detection and location of abnormal part in oil-filled transformers.
Keywords :
chemical analysis; chromatography; condensation; fault diagnosis; insulation testing; mass spectroscopic chemical analysis; power transformer insulation; power transformer testing; transformer oil; condensing analysis; dissolved gases analysis; faults detection; gas chromatography-mass spectrometer; insulating oil diagnosis; oil-filled transformers; purge/trap gas extraction equipment; solid-materials; very small decomposed products; Dissolved gas analysis; Fault detection; Gas insulation; Gases; Oil insulation; Petroleum; Power transformer insulation; Solid modeling; Spectroscopy; Testing;
Conference_Titel :
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN :
0-7803-7525-4
DOI :
10.1109/TDC.2002.1177735