DocumentCode :
3157604
Title :
Chiller Unit Fault Detection and Diagnosis Based on Fuzzy Inference System
Author :
Li, Zhi-sheng ; Zhang, Guo-qiang ; Li, Dong-mei ; Li, Li-juan ; Wu, Jun
Author_Institution :
Coll. of Civil Eng., Hunan Univ., Changsha
Volume :
2
fYear :
2006
fDate :
4-6 Oct. 2006
Firstpage :
1875
Lastpage :
1879
Abstract :
A serials of adverse effects will occur after the chillers units´ production of faults. The chiller units are strong non-linear and long-time delay system, so there are existences of fault detection and diagnosis (FDD) limitation if adoption regular fault judgment method. Fuzzy inference system (FIS) has an outstanding control effect because it is close to human thoughts. Moreover, the result of FIS is easy to be understood by operators. Firstly, fuzzy inference system of chillers unit was modelled in the paper, and then the FIS was trained and checked by the operation data obtained from a real building chiller unit under normal and unhealthy conditions respectively. The results indicated the chillers unit FDD based on FIS is feasible and prompt. Furthermore, this method is simple and prone to be automated.
Keywords :
delay systems; fault diagnosis; fuzzy control; inference mechanisms; FDD; chiller unit fault detection; fault diagnosis; fuzzy inference system; nonlinear system; time delay systems; Civil engineering; Control systems; Degradation; Delay systems; Fault detection; Fault diagnosis; Fuzzy systems; Humans; Refrigeration; System performance;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Computational Engineering in Systems Applications, IMACS Multiconference on
Conference_Location :
Beijing
Print_ISBN :
7-302-13922-9
Electronic_ISBN :
7-900718-14-1
Type :
conf
DOI :
10.1109/CESA.2006.4281944