DocumentCode :
3158234
Title :
Effect of various design parameters on the performance of Gas Insulated Substations (GIS) using Charge Simulation Method
Author :
Subrahmanyam, K.B.V.S.R. ; Amarnath, J.
Author_Institution :
EEE Dept., Vaagdevi Coll. of Eng., Warangal, India
fYear :
2011
fDate :
16-18 Dec. 2011
Firstpage :
1
Lastpage :
4
Abstract :
The Insulation Performance of Compressed Gas Insulated Switchgear and Gas Insulated Transmission Line(GITL) systems can be substantially affected by the presence and movement of metallic particle contaminants. SF6 gas is the main mode of insulation in Gas Insulated Substations(GIS). The voltage withstanding capability of SF6 bus duct is strongly dependent on field perturbations. A method based on particle motion is proposed for determining the movement pattern of metallic particle in Gas Insulated Bus duct(GIB) by considering all the forces acting on the particle like gravitational, drag and the electric field forces. In this work, a single phase of GIB with inner and outer diameter to 55mm and 152mm is considered for the analysis and compared with a single phase enclosure with inner diameter of 70mm and outer diameter of 190mm. Electric fields at the instantaneous contaminated particle locations were computed using Charge Simulation Method (CSM). The simulation carried out for various bus configurations with aluminum, copper and silver wire like particles inside 100KV, 132KV, 145KV and 175KV class enclosure of GIB. The results of the simulation have been presented and analyzed in this paper.
Keywords :
SF6 insulation; aluminium; copper; gas insulated substations; gas insulated switchgear; gas insulated transmission lines; silver; Ag; Al; Cu; GIS; SF6; aluminum wire; charge simulation method; compressed gas insulated switchgear; copper wire; electric fields; field perturbations; gas insulated bus duct; gas insulated substations; gas insulated transmission line; instantaneous contaminated particle locations; insulation performance; metallic particle contaminants; particle motion; silver wire; size 152 mm; size 55 mm; voltage 100 kV; voltage 132 kV; voltage 145 kV; voltage 175 kV; voltage withstanding; Aluminum; Copper; Ducts; Electric fields; Gas insulation; Mathematical model; Silver; Electric field; Gas insulated bus duct; Gas insulated substations; Metallic particles; Particle contamination;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
India Conference (INDICON), 2011 Annual IEEE
Conference_Location :
Hyderabad
Print_ISBN :
978-1-4577-1110-7
Type :
conf
DOI :
10.1109/INDCON.2011.6139569
Filename :
6139569
Link To Document :
بازگشت