DocumentCode
3161584
Title
Evaluation of lightning induced magnetic fields inside reinforced concrete buildings
Author
Miry, Celine ; Amador, Emmanuel ; Duquerroy, P. ; Bachelier, E. ; Prost, D. ; Issac, F.
Author_Institution
EDF R&D, Moret sur Loing, France
fYear
2013
fDate
7-11 Oct. 2013
Firstpage
145
Lastpage
150
Abstract
In this paper, the shielding effectiveness of a reinforced concrete building against lightning induced effects is analyzed. Measurements of magnetic fields induced inside such a structure stressed by a lightning type of aggression are used to setup numerical models of the building with three distinct methods: the method of moments (MoM) with the CDEGS software, the Transmission Line Method (TLM) with CST´s MWS software and LR equivalent circuit simulation technique with ONERA´s LIRIC computer code. Once the limitations of the numerical models are identified, they are used to study the effect of a standard lightning strike in terms of magnetic fields inside the structure.
Keywords
building; lightning protection; magnetic field measurement; magnetic shielding; method of moments; reinforced concrete; transmission lines; CDEGS software; CST MWS software; LR equivalent circuit; MoM; ONERA LIRIC computer code; TLM; lightning strike; magnetic field measurement; method of moments; numerical models; reinforced concrete buildings; shielding; transmission line method; Computational modeling; Floors; Generators; Lightning; Magnetic field measurement; Magnetic fields; lightning currents; magnetic field; numerical analysis; reinforced concrete buildings;
fLanguage
English
Publisher
ieee
Conference_Titel
Lightning Protection (XII SIPDA), 2013 International Symposium on
Conference_Location
Belo Horizonte
Print_ISBN
978-1-4799-1343-5
Type
conf
DOI
10.1109/SIPDA.2013.6729207
Filename
6729207
Link To Document