DocumentCode
3161924
Title
Experimental investigation on altitude correction factor of positive dc corona inception voltages of transmission lines based on the mobile corona cage
Author
Bian, Xingming ; Wang, Liming ; Guan, Zhicheng ; Cao, Jing ; Yang, Yingjian ; WU, Xiong
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beiijing, China
fYear
2010
fDate
11-14 Oct. 2010
Firstpage
548
Lastpage
551
Abstract
In order to obtain the altitude correction factor of corona inception voltage of HVDC transmission lines within the range 23 to 4000 meters, a mobile corona test cage was used to research the influence of altitude changes on positive DC corona characteristics of several kinds of conductors. Photons released as a result of corona discharge on the conductors were detected by the ultraviolet detection apparatus. According to the apparent change of photon number, corona inception voltage could be acquired by the tangent method. With the obtained corona inception voltage in four altitudes, the exponential and linear correction formulas were introduced, which fitted well with the experimental values. Based on the correction relation, a correction coefficient of about -9.5%/1000m was recommended.
Keywords
HVDC power transmission; corona; ultraviolet detectors; HVDC transmission lines; altitude correction factor; corona discharge; mobile corona cage; positive dc corona inception voltages; tangent method; ultraviolet detection apparatus; Conductors; Corona; Discharges; HVDC transmission; Imaging; Photonics; Power transmission lines;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application (ICHVE), 2010 International Conference on
Conference_Location
New Orleans, LA
Print_ISBN
978-1-4244-8283-2
Type
conf
DOI
10.1109/ICHVE.2010.5640704
Filename
5640704
Link To Document