Experimental investigation into the performance of large-scale earthing electrodes
Author
Guo, D. ; Lathi, D. ; Harid, N. ; Griffiths, H. ; Haddad, A. ; Ainsley, A.
Author_Institution
High Voltage Energy Syst. Group, Cardiff Univ., Cardiff, UK
fYear
2010
fDate
11-14 Oct. 2010
Firstpage
465
Lastpage
468
Abstract
Analytical and numerical simulation techniques have been developed for the calculation of earth resistance/impedance and to estimate the potential distribution in the vicinity of earth electrodes. However, very little literature is available on experimental validation of these calculation techniques. To address this, a programme of experimental tests on various earth electrodes has been carried out at the lower water reservoir of a hydro pumped-storage power station in North Wales. In this paper, the earthing test facility at Dinorwig power station is described including the details of the experimental set up. The results from experimental tests on a 5mx5m earth grid, immersed in water and energised are under ac, dc and impulse, are presented. The values of measured earth resistance/impedance and water surface potential distributions are compared with those obtained from analytical calculations and detailed numerical computer simulations.
Keywords
earth electrodes; electric impedance measurement; electrical resistivity; pumped-storage power stations; surface potential; water; earth impedance; earth resistance; earthing test facility; hydro pumped storage power station; large scale earthing electrode; water reservoir; water surface potential distribution; Conductivity; Current measurement; Earth; Electrical resistance measurement; Electrodes; Grounding; Resistance;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application (ICHVE), 2010 International Conference on
Conference_Location
New Orleans, LA
Print_ISBN
978-1-4244-8283-2
Type
conf
DOI
10.1109/ICHVE.2010.5640727
Filename
5640727
Link To Document