  • Abstract
    This paper presents the development of a diagnosis technique, used on-site, applied in the evaluation of station type surge arresters, of SiC and ZnO installed in FURNAS´ electrical system. Thermovision, leakage current and radio interference techniques were used in on-site measurements. From the field results, a statistical study was made and the surge arresters were classified in four categories: suspect, defective, normal and better conditions. After the classification, to evaluate the minimum characteristics of protection, some surge arresters were selected for laboratory tests (flashover voltage, leakage current and residual voltage). After the evaluation of the results, the equipment were opened. The surge arresters´ field diagnosis and their abnormalities were confirmed by the results of laboratory tests and internal visual inspections. It was noticed that for every surge arresters there were abnormalities.
  • Keywords
    arresters; interference (wave); leakage currents; silicon; zinc compounds; FURNAS; diagnosis technique; leakage current; on-site measurements; protection; radio interference techniques; surge arresters; thermovision; Arresters; Current measurement; Laboratories; Leakage current; Surges; Voltage measurement; SiC surge arresters; ZnO surge arresters; diagnosis; leakage current; residual voltage; thermovision;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2010 International Conference on
  • Conference_Location
    New Orleans, LA
  • Print_ISBN
    978-1-4244-8283-2
  • Type

    conf

  • DOI
    10.1109/ICHVE.2010.5640778
  • Filename
    5640778