DocumentCode
3163237
Title
Evaluation and diagnosis technique for surge arresters
Author
Martins, Helvio ; Barbosa, Flávio B. ; Cruz, Waldenir
Author_Institution
CEPEL, Electr. Power Res. Center, Brazil
fYear
2010
fDate
11-14 Oct. 2010
Firstpage
614
Lastpage
617
Abstract
This paper presents the development of a diagnosis technique, used on-site, applied in the evaluation of station type surge arresters, of SiC and ZnO installed in FURNAS´ electrical system. Thermovision, leakage current and radio interference techniques were used in on-site measurements. From the field results, a statistical study was made and the surge arresters were classified in four categories: suspect, defective, normal and better conditions. After the classification, to evaluate the minimum characteristics of protection, some surge arresters were selected for laboratory tests (flashover voltage, leakage current and residual voltage). After the evaluation of the results, the equipment were opened. The surge arresters´ field diagnosis and their abnormalities were confirmed by the results of laboratory tests and internal visual inspections. It was noticed that for every surge arresters there were abnormalities.
Keywords
arresters; interference (wave); leakage currents; silicon; zinc compounds; FURNAS; diagnosis technique; leakage current; on-site measurements; protection; radio interference techniques; surge arresters; thermovision; Arresters; Current measurement; Laboratories; Leakage current; Surges; Voltage measurement; SiC surge arresters; ZnO surge arresters; diagnosis; leakage current; residual voltage; thermovision;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application (ICHVE), 2010 International Conference on
Conference_Location
New Orleans, LA
Print_ISBN
978-1-4244-8283-2
Type
conf
DOI
10.1109/ICHVE.2010.5640778
Filename
5640778
Link To Document