DocumentCode
3163793
Title
Investigation of PD occurrence and detectability in high voltage power cable accessories
Author
Cichecki, Piotr ; Stewayan, Jarot ; Gulski, Edward ; Smit, Johan J. ; Chmura, Lukasz
Author_Institution
Delft Univ. of Technol., Delft, Netherlands
fYear
2010
fDate
11-14 Oct. 2010
Firstpage
264
Lastpage
267
Abstract
The new cable systems are always installed in the field and imperfect assembling of cable accessories could result in the installation defects. The after-laying test is important to certify a good start of the lifetime of the XLPE cable system due to the characteristic of the XLPE insulation which is very sensitive to the PD activity. In this study, the artificial defect that represents PD situation is observed by electric field simulation and different energizing and PD detection methods. Several measurement issues related to the un-conventional PD measurement are also investigated. The investigation of all these important factors is performed to provide a better understanding and performance of PD detection in after-laying test of HV cable system.
Keywords
XLPE insulation; partial discharges; power cable insulation; PD detectability; PD detection methods; PD occurrence; PD situation; XLPE cable system; electric field simulation; high voltage power cable accessories; installation defects; Cable insulation; Electric fields; Energy measurement; Power cables; Sensors; Size measurement; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application (ICHVE), 2010 International Conference on
Conference_Location
New Orleans, LA
Print_ISBN
978-1-4244-8283-2
Type
conf
DOI
10.1109/ICHVE.2010.5640813
Filename
5640813