Partial discharge severity diagnosis and assessment: a case of high-voltage electrode defect in GIS
Author
Qi, Bo ; Li, Chengrong ; Geng, Bibo ; Hao, Zhen ; Chen, Jinxiang ; You, Hao ; Lin, Yihong
Author_Institution
Beijing Key Lab. of High Voltage & EMC, North China Electr. Power Univ., Beijing, China
fYear
2010
fDate
11-14 Oct. 2010
Firstpage
212
Lastpage
215
Abstract
A major cause of insulation failure in GIS equipments is due to the high-voltage electrode defect, which usually occurs at the interface formed by metallic conductor, insulator and SF6. The present research is designed to diagnose and assess the severity levels of the partial discharge (PD) provoked by high-voltage electrode defect on GIS insulator surface. With the application of gradually increased voltage, long term tests were conducted on a well-established 252 kV GIS experiment platform to observe the entire evolution process of partial discharge from its very initiation till the eventual flashover. Real time measurement was also undertaken during the tests to capture the trend curve of partial discharge as a result of test time, the scatter plot, histogram, grey-scale map, and the time-frequency map of the partial discharge. The test results indicate that 1) partial discharge initiated by high-voltage electrode defects undergoes three elocutionary phases, namely, the inception phase, the developing phase and the threatening phase; 2) as partial discharge exacerbates, the phase distribution is widening and corresponding shape changes occur in the scatter plot, histogram, grey-scale map, the time-frequency map and the ultraviolet images. It is suggested that the features of phase distribution and the corresponding spectrums be used as important criterion in diagnosing and assessing the severity levels of the partial discharge triggered by high-voltage electrode defect on GIS insulator surface.
Keywords
SF6 insulation; electrodes; fault diagnosis; gas insulated substations; partial discharges; GIS equipments; GIS experiment platform; GIS insulator surface; SF6; developing phase; grey-scale map; high-voltage electrode defect; histogram; inception phase; insulation failure; metallic conductor; partial discharge severity diagnosis; phase distribution; real time measurement; scatter plot; test time; threatening phase; time-frequency map; ultraviolet images; voltage 252 kV; Acoustics; Discharges; Electrodes; Flashover; Geographic Information Systems; Histograms; Partial discharges; Diagnosis and Assessment; GIS; High-Voltage Electrode Defect; Partial Discharge; Severity;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application (ICHVE), 2010 International Conference on
Conference_Location
New Orleans, LA
Print_ISBN
978-1-4244-8283-2
Type
conf
DOI
10.1109/ICHVE.2010.5640828
Filename
5640828
Link To Document