• DocumentCode
    3164524
  • Title

    Identification of key circuit parameters for the initiation of ferroresonance in a 400-kV transmission system

  • Author

    Ang, Swee Peng ; Peng, Jinsheng ; Wang, Zhongdong

  • Author_Institution
    Univ. of Manchester, Manchester, UK
  • fYear
    2010
  • fDate
    11-14 Oct. 2010
  • Firstpage
    73
  • Lastpage
    76
  • Abstract
    In this paper, the parameters that caused the onset of fundamental (Period-1) ferroresonance upon a 400 kV transmission system are investigated. After validating the developed simulation model by comparing the ferroresonance field test records (voltage and current) with the simulation waveforms, network parameters in particular the capacitances of line are studied. The overall studies suggest that the circuit-to-circuit capacitors dominate the onset of the ferroresonance phenomena whereas the ground and line-to-line capacitors supply additional discharging currents to the core. The study was performed using a computer simulation package called ATPDraw.
  • Keywords
    discharges (electric); ferroresonance; potential transformers; power capacitors; power transmission; circuit-to-circuit capacitors; discharging currents; ferroresonance; line-to-line capacitors; network parameters; simulation waveforms; transmission system; voltage 400 kV; Capacitance; Capacitors; Ferroresonance; Integrated circuit modeling; Power transformers; Power transmission lines; Transformer cores;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    High Voltage Engineering and Application (ICHVE), 2010 International Conference on
  • Conference_Location
    New Orleans, LA
  • Print_ISBN
    978-1-4244-8283-2
  • Type

    conf

  • DOI
    10.1109/ICHVE.2010.5640861
  • Filename
    5640861