DocumentCode
3173741
Title
Lightning impulse performance of air clearances in HV substations
Author
Grzybowski, S. ; Jenkins, E.B. ; Molen, G.M.
Author_Institution
Dept. of Electr. & Comput. Eng., Mississippi State Univ., MS, USA
fYear
1993
fDate
4-7 Apr 1993
Firstpage
0.666666666666667
Abstract
The results of an experimental investigation of the lightning performance of selected electrode configurations as well as 115 kV and 230 kV substation structures are presented. The evaluation of the lightning performance of the air clearances for structures used in HV substations was based on the measured critical flashover voltage (CFO) values for standard 1.2/50 μs lightning impulses with both positive and negative polarities. The measurements of CFO voltages were performed in the Mississippi State University High Voltage Laboratory. The method used for estimating the air clearance in HV substations is discussed. The results obtained enable the designer to optimize air clearances for a specific application
Keywords
HVDC power transmission; flashover; lightning; power system measurement; voltage measurement; 115 kV; 230 kV; HV substations; Mississippi State University; air clearances; critical flashover voltage; electrode configurations; lightning impulse performance; voltage measurement; Electrodes; Flashover; Impulse testing; Insulation; Laboratories; Lightning; Position measurement; Substations; Surge protection; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Southeastcon '93, Proceedings., IEEE
Conference_Location
Charlotte, NC
Print_ISBN
0-7803-1257-0
Type
conf
DOI
10.1109/SECON.1993.465668
Filename
465668
Link To Document