Abstract :
A method for soft-reclosing of fault current limiters (FCLs) is described, which serves to reduce peak currents and stresses on machines when reclosing synchronous generators into an energized power bus and avoid mis-tripping of circuit breakers. This method depends only on local current measurements and is realized by timed closing of parallel switches that are part of the fault current limiter. This soft-reclosing method has been analyzed and verified by simulations. There are reduced currents to avoid the mis-tripping of circuit breakers at interbus cable which splits power sharing network. The voltage and frequency performance are not aggravated by applying the soft-reclosing method.
Keywords :
circuit breakers; electric vehicles; fault current limiters; power system protection; ships; synchronous generators; circuit breakers; electric ship power systems; fault current limiters soft-reclosing; local current measurements; parallel switches timed closing; power bus; synchronous generators; Circuit faults; Control systems; Delay; Fault current limiters; Generators; High temperature superconductors; Power systems;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Ship Technologies Symposium (ESTS), 2011 IEEE
Conference_Location :
Alexandria, VA
Print_ISBN :
978-1-4244-9272-5
Type :
conf
DOI :
10.1109/ESTS.2011.5770875
Filename :
5770875
Link To Document :
بازگشت