DocumentCode
318057
Title
Development of uninterruptible secondary battery system
Author
Ohshima, Masaaki ; Miyazaki, Satoshi ; Inagaki, Katsuhida ; Kikuchi, Hitoshi ; Nirasawa, Hitoshi
Author_Institution
Tokyo Electr. Power Co. Inc., Japan
Volume
2
fYear
1997
fDate
3-6 Aug 1997
Firstpage
707
Abstract
This paper presents the system configuration and control schemes of a USBS (uninterruptible secondary battery system), which acts as a battery energy storage system when no fault occurs in a commercial power network and functions as a UPS in case of network faults. If a fault such as a voltage interruption occurs on the network, the USBS disconnects critical loads from it instantly, and supplies power to them as a UPS. It takes less than 2 ms to restart supply power to the loads in case of an emergency, so no damage occurs. Simulations and experimental tests are carried out to confirm the feasibility of the proposed system
Keywords
battery chargers; electrical faults; power supply circuits; secondary cells; uninterruptible power supplies; UPS; battery energy storage system; critical load disconnection; emergency power supply; uninterruptible secondary battery system; voltage interruption; Batteries; Circuit faults; Control systems; Emergency power supplies; Insulated gate bipolar transistors; Power semiconductor switches; Power supplies; Uninterruptible power systems; Universal Serial Bus; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Conversion Conference - Nagaoka 1997., Proceedings of the
Conference_Location
Nagaoka
Print_ISBN
0-7803-3823-5
Type
conf
DOI
10.1109/PCCON.1997.638286
Filename
638286
Link To Document