Title :
Impact of DFIG windfarms and instrument transformers on transient based protection
Author :
Le Blond, S.P. ; Aggarwal, R.K. ; Abdulhadi, I.F. ; Burtf, G.M.
Author_Institution :
Univ. of Bath, Bath, UK
fDate :
March 29 2010-April 1 2010
Abstract :
The impact of wind generation on high frequency, transient-based overhead line protection is investigated. An 8 bus section of the 132 kV Scottish network with a realistic DFIG-based wind farm model is simulated on a real time digital simulator. Short circuit studies are conducted on a double circuit overhead line adjacent to the wind farm. Three case studies are compared: the DFIG model, a model with instrument transducers and the control model. Analysis is conducted on frequency and time domain voltage and current waveforms measured at the wind farm bus. These show that, compared with the control case, the impact of each case is slight, but the CVT attenuates the higher frequencies of the voltage waveforms slightly more than the DFIG case.
Keywords :
asynchronous generators; instrument transformers; power generation protection; power overhead lines; power transformer protection; short-circuit currents; transient analysis; wind power plants; DFIG-based wind farm model; Scottish network; double circuit overhead line; frequency domain voltage; instrument transducers; instrument transformers; real time digital simulator; short circuit study; time domain voltage; transient based protection; transient-based overhead line protection; voltage 132 kV; voltage waveforms; wind generation; Transient response; instrument transformers; power system simulation; real time systems; wind power generation;
Conference_Titel :
Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on
Conference_Location :
Manchester
DOI :
10.1049/cp.2010.0254