DocumentCode :
3183602
Title :
Islanding detection using an accumulated phase angle drift measurement
Author :
Yip, H.T. ; Millar, G. ; Lloyd, G.J. ; Dysko, A. ; Burt, G.M. ; Tumilty, R.
Author_Institution :
AREVA T&D UK Ltd., Stafford, UK
fYear :
2010
fDate :
March 29 2010-April 1 2010
Firstpage :
1
Lastpage :
5
Abstract :
Distributed generation is increasingly likely to play a major role in electricity supply systems as recognition is made of its low carbon credentials. However, the integration of these units at distribution voltages is a major challenge for utilities. One particular issue is that generators may, unintentionally, continue to supply local demand when areas of the network are isolated from the main system. Reliably detecting this condition is regarded by many as an ongoing challenge as existing methods are not entirely satisfactory. This paper proposes a novel method based on accumulated phase angle drift that provides inherently enhanced stability without unduly sacrificing sensitivity. It is passive and thus requires no additional invasive hardware. Transient simulations are used to demonstrate its performance.
Keywords :
angular measurement; distributed power generation; electricity supply industry; phase measurement; voltage distribution; accumulated phase angle drift measurement; additional invasive hardware; distributed generation; distribution voltages; electricity supply systems; islanding detection; low carbon credentials; phase angle drift; supply local demand; transient simulations; unduly sacrificing sensitivity; digital transient simulation; distributed generation; loss of grid; power system relaying;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on
Conference_Location :
Manchester
Type :
conf
DOI :
10.1049/cp.2010.0242
Filename :
5522144
Link To Document :
بازگشت