DocumentCode :
3184730
Title :
Validation of a novel unit protection scheme based on superimposed fault currents
Author :
Thomas, D.W.P. ; Christopoulos, C. ; Tang, Y. ; Gale, P.
Author_Institution :
Nottingham Univ., UK
fYear :
2001
fDate :
2001
Firstpage :
185
Lastpage :
188
Abstract :
This paper presents a novel unit protection scheme which is based on the directional information contained in the superimposed currents created by a fault alone. If, at a connecting busbar more than two transmission lines are monitored, it is shown that the superimposed currents alone are sufficient to give directional information for a unit scheme. Current transformers have a much greater bandwidth than voltage transformers, so this scheme has a much faster response time than comparable unit schemes which require both voltage and current information. Results, using recorded transients from events on a real 400 kV transmission system, are given to demonstrate the potential of this scheme. The scheme is simple, reliable and ultra fast. It is suitable for long transmission lines and its speed is limited only by the communications channel
Keywords :
busbars; current transformers; power system transients; power transmission faults; power transmission lines; power transmission protection; 400 kV; busbar; communications channel; current transformers; superimposed fault currents; transmission lines; transmission network transients; unit protection scheme validation;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection, 2001, Seventh International Conference on (IEE)
Conference_Location :
Amsterdam
ISSN :
0537-9989
Print_ISBN :
0-85296-732-2
Type :
conf
DOI :
10.1049/cp:20010131