Abstract :
The paper will present a utility experience from a project where protection and control for the whole substation is done by using IEC 61850 standard. The special attention will be given to the control of parallel transformers with on-load tapchanger (OLTC), which has been achieved by using IEC 61850 analogue GOOSE messages between the regulators. In this substation, there are two 20 MVA, 110/20kV, YNd5 transformers with OLTC. Each power transformer has a dedicated IED which provides integrated protection and control for the transformer. Thus, all power transformer protection functions like 87T, 87 N, 50/51, 50N/51N, 49 as well as OLTC control function 90 are integrated into a single device. Transformer backup protections are allocated in the additional protection device (50N/51N) and in busbar protection bay unit (21T, 50/51) for the transformer bay. Because the two transformers can operate in parallel, the OLTC control is based on the minimizing circulating current principle. The OLTC control functionality is implemented in accordance with IEC 61850 Standard. Thus, two logical nodes, namely YLTC and ATCC, are available in each of the two IEDs. The YLTC logical nodes represents the OLTC mechanism and integrate functionality like tap position reading, OLTC mechanism supervision and issuing of the manual and automatic raise and lower commands to the OLTC mechanism. The ATCC logical node represents the regulator itself and integrates functionality like voltage measurement and supervision, timing, line drop compensation, circulating current measurement and compensation etc. Because of the parallel control it is necessary to exchange information about measured current, measured voltage, etc. between the two IEDs. This information exchange is performed by using analog GOOSE messages in accordance with IEC 61850 Standard bet
Keywords :
IEC standards; busbars; on load tap changers; power transformer protection; substation protection; ATCC logical nodes; IEC 61850 analogue GOOSE messages; OLTC control; OLTC control functionality; YLTC logical nodes; YNd5 transformers; apparent power 20 MVA; busbar protection bay unit; current measurement; external system integrator; line drop compensation; on-load tap changer; on-load voltage control; parallel control; parallel transformers; power transformer protection; protection device; regulators; substation; transformer backup protections; voltage 110 kV; voltage 20 kV; voltage measurement; Analogue GOOSE message; Automatic On-load Tap-Changer control; Power Transformer Control;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection (DPSP 2010). Managing the Change, 10th IET International Conference on
Conference_Location :
Manchester
Type :
conf
DOI :
10.1049/cp.2010.0227
Filename :
5522229
Link To Document :
بازگشت