Abstract :
In today´s competitive environment, investments must have a minimum global cost. For protection relays, as for any other electrical device, users need standard, packaged solutions, with a minimum engineering study. Restricted earth fault (REF) protection, as other protections, is a good candidate because it needs no time grading study. Evolution in computer relaying have made this protection available in a multi-functional device for transformer application. In such an implementation a low impedance principle is used. No external stabilising resistor nor class X CTs are needed, making the installation of the protection straightforward. It is thus possible to build a fully packaged cubicle for transformer protection, including CTs and multifunctional relay giving improved transformer protection thanks to a REF protection
Keywords :
current transformers; electric impedance; power transformer protection; relay protection; computer relaying; low impedance principle; low impedance restricted earth fault protection; multi-functional device; multifunctional relay; packaged cubicle; protection installation; protection relays; transformer application; transformer protection;
Conference_Titel :
Developments in Power System Protection, 2001, Seventh International Conference on (IEE)
Conference_Location :
Amsterdam
Print_ISBN :
0-85296-732-2
DOI :
10.1049/cp:20010203