• DocumentCode
    3186019
  • Title

    Low impedance restricted earth fault protection

  • Author

    Bertrand, P. ; Gotzig, B. ; Vollet, C.

  • Author_Institution
    Schneider Electr., France
  • fYear
    2001
  • fDate
    2001
  • Firstpage
    479
  • Lastpage
    482
  • Abstract
    In today´s competitive environment, investments must have a minimum global cost. For protection relays, as for any other electrical device, users need standard, packaged solutions, with a minimum engineering study. Restricted earth fault (REF) protection, as other protections, is a good candidate because it needs no time grading study. Evolution in computer relaying have made this protection available in a multi-functional device for transformer application. In such an implementation a low impedance principle is used. No external stabilising resistor nor class X CTs are needed, making the installation of the protection straightforward. It is thus possible to build a fully packaged cubicle for transformer protection, including CTs and multifunctional relay giving improved transformer protection thanks to a REF protection
  • Keywords
    current transformers; electric impedance; power transformer protection; relay protection; computer relaying; low impedance principle; low impedance restricted earth fault protection; multi-functional device; multifunctional relay; packaged cubicle; protection installation; protection relays; transformer application; transformer protection;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2001, Seventh International Conference on (IEE)
  • Conference_Location
    Amsterdam
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-732-2
  • Type

    conf

  • DOI
    10.1049/cp:20010203
  • Filename
    929367