  • Title

    Zero-sequence voltages in unit-connected generator for different methods of grounding generator neutral

  • Author

    Fulczyk, M.

  • Author_Institution
    ABB Corp. Res., Krakow, Sweden
  • fYear
    2001
  • fDate
    2001
  • Firstpage
    499
  • Lastpage
    502
  • Abstract
    In this paper, the influence of parameters of the generator and transformer, the additional capacitance to ground of the generator breakers on the zero-sequence voltages in generators during faults in the stator winding and the power system was determined. The analysis of zero-sequence components was carried out for unit-connected generators of power up to 1200 MVA. The voltage zero-sequence components feeding the measuring element of the protections were determined at faults along the whole length of the generator stator winding
  • Keywords
    earthing; electric generators; electrical faults; machine protection; machine theory; power transformer protection; stators; generator breaker capacitance; generator neutral grounding methods; power system; stator winding faults; unit-connected generator protection; voltage zero-sequence components; zero-sequence voltages;