DocumentCode :
3190772
Title :
Harmonic Current Injection for Varying Rectifier Loads
Author :
Singh, Bhim ; Bhuvaneswari, G. ; Garg, Vipin
fYear :
2005
fDate :
11-13 Dec. 2005
Firstpage :
143
Lastpage :
147
Abstract :
This paper presents a novel method of reducing harmonic currents at the point of common coupling (PCC) in a three-phase diode bridge rectifier type utility interface. The proposed configuration consists of a current injection device, a newly designed current injection network and a properly tuned passive shunt filter. The paper also presents the design details of the current injection network and the passive filter. The proposed configuration performs well under varying loads on the rectifier. The effect of load variation on rectifier is also studied to demonstrate the effectiveness of the proposed ac-dc converter. A set of power quality indices on input ac mains and on dc bus is also presented.
Keywords :
Harmonic current injection; power quality improvement; rectifier load; AC-DC power converters; Bridge circuits; Light emitting diodes; Load management; Passive filters; Power harmonic filters; Power quality; Power system harmonics; Rectifiers; Voltage; Harmonic current injection; power quality improvement; rectifier load;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
INDICON, 2005 Annual IEEE
Print_ISBN :
0-7803-9503-4
Type :
conf
DOI :
10.1109/INDCON.2005.1590142
Filename :
1590142
Link To Document :
بازگشت