DocumentCode
3194398
Title
Recovery conditions for AC arc on ice surfaces
Author
Chen, X. ; Farzaneh, M. ; Zhang, J.
Author_Institution
Quebec Univ., Chicoutimi, Que., Canada
fYear
1995
fDate
22-25 Oct 1995
Firstpage
396
Lastpage
399
Abstract
This paper presents the results of research undertaken with the aim of obtaining the recovery conditions for an AC arc on iced surfaces. Using a cylindrical ice sample, the relationship linking the arc current, minimum arc recovery voltages and the voltage across the arc may be obtained. The results provided by this model may be used to calculate the AC flashover voltage of industrial ice-covered insulators
Keywords
arcs (electric); flashover; ice; insulators; recovery; surface discharges; AC arc recovery conditions; AC flashover voltage; arc current; cylindrical ice sample; ice surfaces; industrial ice-covered insulators; minimum arc recovery voltages; outdoor insulators; Air gaps; Circuit testing; Flashover; Ice surface; Insulation; Pollution; Surface contamination; Surface discharges; Surface resistance; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 1995. Annual Report., Conference on
Conference_Location
Virginia Beach, VA
Print_ISBN
0-7803-2931-7
Type
conf
DOI
10.1109/CEIDP.1995.483746
Filename
483746
Link To Document