Abstract
This paper discusses the ramifications of grounding a substation power transformer through a reactor on the CenterPoint Energy distribution system. The purpose of the reactor is to reduce the magnitude of ground fault currents. This is expected to increase transformer life expectancy by significantly reducing transformer short circuit forces. The higher ground impedance provided by the neutral grounding reactor (NGR) also causes an increased voltage drop in the ground return path, raising the temporary overvoltage on the unfaulted phases and deepening the voltage sag on the faulted phase during a ground fault. Under normal operating conditions with large load imbalances, voltage regulation can be also impacted. The reduction in ground fault current requires the modification of ground protective device coordination and settings. The paper discusses how these issues are addressed for a successful implementation of an NGR in an effectively grounded, 4-wire distribution system.
Keywords
earthing; failure analysis; fault currents; overvoltage protection; power distribution protection; power supply quality; power transformer protection; substation protection; transformer substations; voltage control; 4-wire distribution system; CenterPoint Energy distribution system; NGR; ground fault; ground fault current; ground fault current reduction; ground impedance; ground protective device coordination; ground return path; neutral grounding reactor; substation power transformer; temporary overvoltage; transformer short circuit force; voltage drop; voltage regulation; voltage sag; Circuit faults; Fault currents; Grounding; Impedance; Inductors; Power system protection; Power transformers; Substation protection; Voltage control; Voltage fluctuations;
fLanguage
English
Publisher
ieee
Conference_Titel
Protective Relay Engineers, 2005 58th Annual Conference for
Print_ISBN
0-7803-8896-8
Type
conf
DOI
10.1109/CPRE.2005.1430419
Filename
1430419
Link To Document