• DocumentCode
    3197516
  • Title

    System protection and control task force´s initial recommendations concerning NERC recommendation 8A loadability requirements on transmission protective relaying systems

  • Author

    Carpenter, M.

  • fYear
    2005
  • fDate
    5-7 April 2005
  • Firstpage
    250
  • Lastpage
    257
  • Abstract
    This paper discusses with system protection and control task force´s initial recommendations concerning with NERC recommendation 8A loadability requirements on transmission protective relaying systems. The NERC investigation team recommends that the zone 3 relay, if used, should not operate at or below 150% of the emergency ampere rating of a line, assuming a .85 per unit voltage and a line phase angle of 30 degrees. The planning committee shall review such exceptions to ensure they do not increase the risk of widening a cascading failure of the power system.
  • Keywords
    power system relaying; power transmission lines; power transmission planning; power transmission protection; relay protection; risk analysis; 8A loadability; NERC recommendation; cascading failure; control task; emergency ampere rating; line phase angle; planning committee shall; power system risk; transmission protective relaying systems; Call conference; Certification; Control systems; Electrical equipment industry; Force control; Power system planning; Power system relaying; Protection; Protective relaying; Relays;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Protective Relay Engineers, 2005 58th Annual Conference for
  • Print_ISBN
    0-7803-8896-8
  • Type

    conf

  • DOI
    10.1109/CPRE.2005.1430438
  • Filename
    1430438