• DocumentCode
    3198576
  • Title

    Operational Experience of Cooling Water Systems for Accelerator Components at PLS

  • Author

    Kim, K.R. ; Kim, H.G. ; Lee, B.H. ; Han, H.S. ; Chung, C.W. ; Kim, Y.C. ; Ko, I.S.

  • Author_Institution
    PAL/POSTECH, Pohang, 790-784, Korea, krk0301@postech.ac.kr
  • fYear
    2005
  • fDate
    16-20 May 2005
  • Firstpage
    850
  • Lastpage
    852
  • Abstract
    The PLS cooling water system has been utilized for absorbing thermal load generated by a multitude of electromagnetic rf power delivering networks at PLS. The low conductivity cooling water for heat removal from the accelerator components is deionised and filtered to more than 2 MΩ·cm of specific resistance. The operation temperature of dedicated components in the accelerator is sustained as tight as ±0.1°C to minimize the influence of temperature fluctuation on the beam energy and stability. Although the PLS cooling systems were initially installed with a high degree of flexibility to allow for the conditioned operations for high beam gain, the system improvements and repairs have been employed to enhance the operational performance and reliability, and to incorporate the newly developed operating interfaces such as EPICS accelerator control systems.
  • Keywords
    Conductivity; Cooling; Fluctuations; Particle beams; Power generation; Resistance heating; Stability; Temperature; Thermal loading; Water heating;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Particle Accelerator Conference, 2005. PAC 2005. Proceedings of the
  • Print_ISBN
    0-7803-8859-3
  • Type

    conf

  • DOI
    10.1109/PAC.2005.1590586
  • Filename
    1590586