DocumentCode :
3199977
Title :
High Precision Temperature Control and Analysis of RF Deionized Cooling Water System
Author :
Tsai, Z.D. ; Chang, J.C. ; Liu, C.Y. ; Chen, J.R.
Author_Institution :
National Synchrotron Radiation Research Center, Hsinchu 30076, Taiwan, R. O. C. e-mail: ZDTsai@nsrrc.org.tw
fYear :
2005
fDate :
16-20 May 2005
Firstpage :
1057
Lastpage :
1059
Abstract :
Previously, the Taiwan Light Source (TLS) has proven the good beam quality mainly depends on the utility system stability. A series of efforts were devoted to these studies. Further, a high precision temperature control of the RF de-ionized cooling water system has been achieved to meet the more critical stability requirement. The paper investigates the mixing mechanism through thermal and flow analysis and verifies the practical influences. A flow mixing mechanism and control philosophy is studied and processed to minimize temperature variation which has been reduced from ± 0.1 °C to ± 0.01 °. Also, the improvement of correlation between RF performance and water cooling stability is presented.
Keywords :
Control system analysis; Cooling; Heat pumps; Light sources; Radio frequency; Stability; Temperature control; Temperature sensors; Valves; Water heating;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Particle Accelerator Conference, 2005. PAC 2005. Proceedings of the
Print_ISBN :
0-7803-8859-3
Type :
conf
DOI :
10.1109/PAC.2005.1590657
Filename :
1590657
Link To Document :
بازگشت