An efficient cooling system for telecommunication equipment rooms
Author
Nakao, Nasaki ; Hayama, Hirofumi ; Uekusa, Tsuneo
Author_Institution
NTT, Tokyo, Japan
fYear
1988
fDate
30 Oct-2 Nov 1988
Firstpage
344
Lastpage
349
Abstract
The evaluation of air-flow systems for telecommunication equipment rooms was carried out experimentally. Parameters were room air temperature distribution and ambient temperature of electric parts, i.e. air temperature around circuit boards, which are influenced by an air-flow system. The under-floor air supply and overhead return system has shown to be superior to other flow systems and its allowable average heat density was up to 1.1 kW/m2. A microcomputer control unit was developed for the cooling unit. It is shown that this control can optimize the refrigeration cycle of the cooling unit under low outdoor air temperature, minimizing running costs
Keywords
cooling; microcomputer applications; telecommunication equipment; thermal variables control; air-flow systems; ambient temperature; cooling system; microcomputer control unit; overhead return system; refrigeration cycle; room air temperature distribution; telecommunication equipment rooms; under-floor air supply; Cooling; ISDN; Ice; Microcomputers; Printed circuits; Resistance heating; Switches; Telecommunication switching; Telegraphy; Temperature control;