• DocumentCode
    3210080
  • Title

    The practice of ground differential relaying

  • Author

    Nichols, W.H. ; Cosse, R.E., Jr.

  • Author_Institution
    Westinghouse Electr. Corp., Houston, TX, USA
  • fYear
    1988
  • fDate
    12-14 Sep 1988
  • Firstpage
    21
  • Lastpage
    28
  • Abstract
    The basic concepts are presented of ground differential protection for transformers and generators. Ground differential relaying provides fast and sensitive ground fault protection for wye-connected and ground electrical power equipment such as rotating generators or power transformers. Because it is a differential system, there is no need to incorporate undesirable time delay or to sacrifice sensitivity for the sake of system coordination. The authors first explain ground differential relaying for power transformers and generators, and then explain the ground differential scheme using a commercially available product type relay. Finally, they illustrate a method of current transformer selection that will help better implementation of the ground differential scheme
  • Keywords
    electric generators; power transformers; relay protection; substations; generator protection; ground differential relaying; sensitivity; time delay; transformer protection; Current transformers; Delay effects; Power generation; Power system protection; Power system relaying; Power transformers; Protective relaying; Relays; Reliability engineering; Substation protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Conference, 1988, Record of Conference Papers., Industrial Applications Society 35th Annual
  • Conference_Location
    Dallas, TX
  • Type

    conf

  • DOI
    10.1109/PCICON.1988.22413
  • Filename
    22413