• DocumentCode
    3211770
  • Title

    Improving capacitive voltage transformer response and its impact on distance relay performance

  • Author

    Zare, Mohammad Hadi ; Mirzaei, Ahmad ; Abyaneh, Hossein Askarian

  • Author_Institution
    Yazd Univ., Yazd, Iran
  • fYear
    2012
  • fDate
    15-17 May 2012
  • Firstpage
    523
  • Lastpage
    528
  • Abstract
    Capacitive voltage transformer (CVT) has an ideal steady state response at the system power frequency, while its dynamic response is inferior. This may lead to the mis-operation of distance relays during a fault. This paper presents a new method in order to correct CVT transient response. The proposed method is able to eliminate transients emerging in the CVT output for various fault conditions and CVT parameters in the real-time. The simulation results reveal that the modified CVT exhibits a low percentage error. Moreover, the percentage overreach of distance relay connected to the modified CVT is considerably reduced.
  • Keywords
    fault diagnosis; potential transformers; relay protection; transient response; CVT transient response; capacitive voltage transformer response; distance relay protection performance; dynamic response; fault conditions; system power frequency; Inductance; Relays; Capacitive Voltage Transformer; Distance Relay; Overreach; Transient Response;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Engineering (ICEE), 2012 20th Iranian Conference on
  • Conference_Location
    Tehran
  • Print_ISBN
    978-1-4673-1149-6
  • Type

    conf

  • DOI
    10.1109/IranianCEE.2012.6292413
  • Filename
    6292413