DocumentCode
3213788
Title
Comparison of control strategies for active power filter in three-phase four-wire systems
Author
Ma, Hao ; Cai, Zheng
Author_Institution
Coll. of Electr. Eng., Zhejiang Univ., Hangzhou, China
Volume
2
fYear
2004
fDate
2-6 Nov. 2004
Firstpage
1429
Abstract
This paper analyzed three control strategies (direct power control, per-phase harmonic reference generation method, conventional Ip-Iq method) for active power filters in three-phase four-wire systems. They were applied to a 4-leg inverter to compensate input currents of an office building. Differences in harmonic detecting and switching sequence generation of these three control strategies were analyzed. Per-phase harmonic reference generation control is used to reduce capacity of dc bus capacitor. Direct power control is designed for better harmonic compensation as well as smaller power capacity. The simulation results are presented to substantiate the theoretical analyses.
Keywords
active filters; capacitors; control system synthesis; invertors; power control; power harmonic filters; active power filter; conventional Ip-Iq method; dc bus capacitor; direct power control design; four leg inverter; harmonic compensation; perphase harmonic reference generation method; switching sequence generation; three-phase four-wire systems; Active filters; Buildings; Control system analysis; Control systems; Harmonic analysis; Inverters; Power control; Power generation; Power harmonic filters; Power system harmonics;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial Electronics Society, 2004. IECON 2004. 30th Annual Conference of IEEE
Print_ISBN
0-7803-8730-9
Type
conf
DOI
10.1109/IECON.2004.1431788
Filename
1431788
Link To Document