DocumentCode :
3216634
Title :
Evaluation of clock synchronization accuracy of coexistent Real-Time Ethernet protocols
Author :
Ferrari, P. ; Flammini, A. ; Rinaldi, S. ; Gaderer, G.
Author_Institution :
Univ. of Brescia, Brescia
fYear :
2008
fDate :
22-26 Sept. 2008
Firstpage :
87
Lastpage :
91
Abstract :
This paper investigates Real-Time Ethernet (RTE) protocols for industrial applications and their clock synchronization performance. In fact, if different RTE protocols coexist on the same network sharing the same infrastructure, clock synchronization capabilities can be affected. This paper introduces a simulation environment to evaluate coexistence of RTE protocols. The proposed tool is described and validated by comparison with measurement data taken from real networks. Finally, simulation results are presented: the behavior of Ethernet/IP with IEEE1588-PTP, when it is transported over an isochronous PROFINET IO network, is shown and some improvements to the PTP tracking algorithms to ease coexistence are proposed.
Keywords :
local area networks; real-time systems; transport protocols; clock synchronization accuracy; industrial automation; real-time Ethernet protocols; Access protocols; Automation; Clocks; Communication system control; Ethernet networks; IEC standards; Instruments; Synchronization; Testing; Time division multiple access; Clock synchronization; Coexistence; Industrial Automation; Real-Time Ethernet; Simulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Precision Clock Synchronization for Measurement, Control and Communication, 2008. ISPCS 2008. IEEE International Symposium on
Conference_Location :
Ann Arbor, MI
Print_ISBN :
978-1-4244-2274-6
Electronic_ISBN :
978-1-4244-2275-3
Type :
conf
DOI :
10.1109/ISPCS.2008.4659219
Filename :
4659219