DocumentCode
322602
Title
Service experience for XLPE cables installed in Norway - from graphite painted insulation screens to axially and radially water tight cable constructions
Author
Faremo, H. ; Benjaminsen, J.T. ; Larsen, P.B. ; Tunheim, A.
Author_Institution
Norwegian Electr. Power Res. Inst., Trondheim, Norway
Volume
3
fYear
1997
fDate
1997
Firstpage
42401
Abstract
XLPE power cables were introduced in Norway by Alcatel Kabel Norge AS in 1968. The standard XLPE construction sold to the Norwegian electric utilities today is an axially and radially watertight power cable construction presented in 1991. The objective of this paper is to summarize test results that show the development steps of the Norwegian XLPE power cable and combine this with the actual service performance presented in the Norwegian XLPE power cable failure statistics. The report shows that the long term wet ageing performance of power cables produced today is significantly improved compared to cables produced in the 1970s and 80s. Still, however, water trees do initiate in the new power cables if they are subjected to long term ageing tests. Therefore in order to ensure an entirely watertight cable, an aluminium foil under the PE-sheath is presented as the standard XLPE power cable in Norway today. More than 80% of the MV power cable market are using this cable construction in their power networks
Keywords
XLPE insulation; MV power cable; Norway; XLPE power cables; aluminium foil; electric utilities; long term wet ageing performance; service experiences; service performance; sheath; test results; water trees; watertight power cable construction;
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution. Part 1: Contributions. CIRED. 14th International Conference and Exhibition on (IEE Conf. Publ. No. 438)
Conference_Location
Birmingham
ISSN
0537-9989
Print_ISBN
0-85296-674-1
Type
conf
DOI
10.1049/cp:19970510
Filename
667949
Link To Document