DocumentCode
322623
Title
Evaluation of the sealing system and of the electric performance of the distribution lightning arresters
Author
Campos, M.L.B.
Author_Institution
CESP, Sao Paulo
Volume
3
fYear
1997
fDate
1997
Abstract
After certifying the unsatisfactory performance of the lightning arresters and identifying the moisture penetration as the main cause, a methodology for the sealing evaluation of such lightning arresters was researched and developed. Moreover, the electric conditions of the lightning arresters in the manufacturing line and in the stocks of concessionaires (new ones) were verified and still those taken out of operation in networks and by operation of the automatic disconnector or internal criteria of the concessionaires (used ones)
Keywords
distribution networks; automatic disconnector; distribution network lightning arresters; electric performance; moisture penetration; sealing system evaluation;