DocumentCode
322947
Title
Pressure stress of switchgear and compact substations in case of internal arcs
Author
Drescher, G. ; Späck, H. ; Betzmann, M. ; Müller, H.
Author_Institution
Siemens AG, Germany
Volume
1
fYear
1997
fDate
1997
Firstpage
42614
Abstract
The internal arc tests of compact substations to prove the safety of personnel in case of internal arcs can be divided in two separate tests if there are maximum permitted values of pressure stress in the different compartments. To ensure that the pressure stress is lower than the pressure withstand capability, pressure relief devices and pressure reducing means are necessary. Under these conditions, the pressure withstand capability of the housing of the compact substation and the incorporated medium voltage switchgear can be tested with simplified, minor expensive tests. However, tests to prove the impact of hot arc gases requires tests under real conditions
Keywords
substations; SF6; SF6-insulated medium voltage switchgear; compact substations; internal arcs; personnel safety; pressure reducing means; pressure relief devices; pressure withstand capability; switchgear pressure stress tests;
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution. Part 1: Contributions. CIRED. 14th International Conference and Exhibition on (IEE Conf. Publ. No. 438)
Conference_Location
Birmingham
ISSN
0537-9989
Print_ISBN
0-85296-674-1
Type
conf
DOI
10.1049/cp:19970449
Filename
671629