• DocumentCode
    322947
  • Title

    Pressure stress of switchgear and compact substations in case of internal arcs

  • Author

    Drescher, G. ; Späck, H. ; Betzmann, M. ; Müller, H.

  • Author_Institution
    Siemens AG, Germany
  • Volume
    1
  • fYear
    1997
  • fDate
    1997
  • Firstpage
    42614
  • Abstract
    The internal arc tests of compact substations to prove the safety of personnel in case of internal arcs can be divided in two separate tests if there are maximum permitted values of pressure stress in the different compartments. To ensure that the pressure stress is lower than the pressure withstand capability, pressure relief devices and pressure reducing means are necessary. Under these conditions, the pressure withstand capability of the housing of the compact substation and the incorporated medium voltage switchgear can be tested with simplified, minor expensive tests. However, tests to prove the impact of hot arc gases requires tests under real conditions
  • Keywords
    substations; SF6; SF6-insulated medium voltage switchgear; compact substations; internal arcs; personnel safety; pressure reducing means; pressure relief devices; pressure withstand capability; switchgear pressure stress tests;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution. Part 1: Contributions. CIRED. 14th International Conference and Exhibition on (IEE Conf. Publ. No. 438)
  • Conference_Location
    Birmingham
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-674-1
  • Type

    conf

  • DOI
    10.1049/cp:19970449
  • Filename
    671629