DocumentCode :
322986
Title :
A philosophy and algorithms for extinguishing earth fault arcs in suppressed medium voltage networks
Author :
Nikander, A. ; Lakervi, E.
Author_Institution :
Tampere Univ. of Technol., Finland
Volume :
4
fYear :
1997
fDate :
1997
Abstract :
The compensation of earth fault current in medium voltage power networks can be carried out either centrally or by using more cost-effective decentralized compensation. This paper introduces a novel cost-effective principle for increasing the compensation degree and selecting the tripping range of earth fault relays in originally partially compensated or isolated power systems. This has an essentially positive effect on the reduction of short interruptions to customers. Earth faults in compensated systems are simulated by the ATP version of the well-known EMTP program and the results are compared to field measurements. Conditions in radially operated rural 20 kV overhead line networks are considered
Keywords :
distribution networks; 20 kV; ATP software; MV power networks; compensation degree; earth fault current compensation; field measurements; power distribution protection; rural overhead distribution line networks; short interruptions; tripping range;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution. Part 1: Contributions. CIRED. 14th International Conference and Exhibition on (IEE Conf. Publ. No. 438)
Conference_Location :
Birmingham
ISSN :
0537-9989
Print_ISBN :
0-85296-674-1
Type :
conf
DOI :
10.1049/cp:19970570
Filename :
671674
Link To Document :
بازگشت