DocumentCode
3238243
Title
The influence of SICSFCL and the relationship between SICSFCL and distance relay protection of power grid
Author
Cui, Ji Bin ; Sun, Yu Wei ; Hong, Hui ; Gong, Wei Zhi ; Xin, Ying ; Wang, Jian Zhong ; Xiong, Zhi Quan ; Zi, Mei Rong ; Hu, Chang Bin
Author_Institution
Innopower Supercond. Cable Co., Ltd., Beijing, China
fYear
2011
fDate
14-16 Dec. 2011
Firstpage
301
Lastpage
304
Abstract
A Saturated Iron Core Superconducting Fault Current Limiter (SICSFCL) provides a powerful fault current limitation in high voltage and high capacity power grid. A 35kV/90MVA SICSFCL was installed in a 35 kV network for live-grid operation, in January 2008 at Puji substation, Kunming, China. With deep research on SICSFCL, the matching problem between SICSFCL and relay protection currently needs to be solved. This paper analyzes the influence that SICSFCL brings to the distance relay protection which is used widely in high voltage power grid, and considering the characteristics of microcomputer-based protection, this paper proposes a new algorithm to eliminate the influence.
Keywords
power grids; power system protection; relay protection; superconducting fault current limiters; SICSFCL; apparent power 90 MVA; distance relay protection; high capacity power grid; high voltage power grid; live-grid operation; saturated iron core superconducting fault current limiter; voltage 35 kV; Circuit faults; Fault currents; Impedance; Power grids; Power system stability; Protective relaying; fault current limiter; relay protection; superconducting devices;
fLanguage
English
Publisher
ieee
Conference_Titel
Applied Superconductivity and Electromagnetic Devices (ASEMD), 2011 International Conference on
Conference_Location
Sydney, NSW
Print_ISBN
978-1-4244-7852-1
Type
conf
DOI
10.1109/ASEMD.2011.6145128
Filename
6145128
Link To Document