• DocumentCode
    3238243
  • Title

    The influence of SICSFCL and the relationship between SICSFCL and distance relay protection of power grid

  • Author

    Cui, Ji Bin ; Sun, Yu Wei ; Hong, Hui ; Gong, Wei Zhi ; Xin, Ying ; Wang, Jian Zhong ; Xiong, Zhi Quan ; Zi, Mei Rong ; Hu, Chang Bin

  • Author_Institution
    Innopower Supercond. Cable Co., Ltd., Beijing, China
  • fYear
    2011
  • fDate
    14-16 Dec. 2011
  • Firstpage
    301
  • Lastpage
    304
  • Abstract
    A Saturated Iron Core Superconducting Fault Current Limiter (SICSFCL) provides a powerful fault current limitation in high voltage and high capacity power grid. A 35kV/90MVA SICSFCL was installed in a 35 kV network for live-grid operation, in January 2008 at Puji substation, Kunming, China. With deep research on SICSFCL, the matching problem between SICSFCL and relay protection currently needs to be solved. This paper analyzes the influence that SICSFCL brings to the distance relay protection which is used widely in high voltage power grid, and considering the characteristics of microcomputer-based protection, this paper proposes a new algorithm to eliminate the influence.
  • Keywords
    power grids; power system protection; relay protection; superconducting fault current limiters; SICSFCL; apparent power 90 MVA; distance relay protection; high capacity power grid; high voltage power grid; live-grid operation; saturated iron core superconducting fault current limiter; voltage 35 kV; Circuit faults; Fault currents; Impedance; Power grids; Power system stability; Protective relaying; fault current limiter; relay protection; superconducting devices;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Applied Superconductivity and Electromagnetic Devices (ASEMD), 2011 International Conference on
  • Conference_Location
    Sydney, NSW
  • Print_ISBN
    978-1-4244-7852-1
  • Type

    conf

  • DOI
    10.1109/ASEMD.2011.6145128
  • Filename
    6145128