  • Abstract
    Flexible AC Transmission System (FACTS) devices are inserted into power grids in series, in shunt, and in some cases, both in shunt and series for the improved power transmission capability. They also improve the controllability, stability and power quality of the power system. Static Synchronous Compensator (STATCOM) is a shunt type FACTS device connected at the midpoint of the transmission line to maintain the voltage at desired level by injecting/absorbing the reactive power. These devices have fast dynamic response time, which overlap with the response time of the line protection distance relays. This interaction affects the performance of distance protection relay during line faults. In this paper the design and development of a new adaptive distance relaying scheme to mitigate the adverse effects of the STATCOM is presented. A ±100MVA 48 pulse STATCOM with associated control system, connected at the midpoint of a typical 400KV transmission system is selected for simulation. The line faults of different types at various locations of the line are simulated using EMTDC/PSCAD® and the performance of newly developed adaptive distance protection scheme has been evaluated and efficacy of the proposed scheme is illustrated.
  • Keywords
    CAD; flexible AC transmission systems; power engineering computing; power grids; power supply quality; power transmission faults; power transmission lines; static VAr compensators; EMTDC-PSCAD; FACTS; STATCOM; adaptive distance relay; apparent power -100 MVA; apparent power 100 MVA; dynamic response time; flexible AC transmission system devices; line faults; power grids; power quality; power system; power transmission capability; stability; static synchronous compensator; voltage 400 kV; Automatic voltage control; Impedance; Mathematical model; Power transmission lines; Protective relaying; 48 pulse STATCOM; Adaptive distance relay; EMTDC/PSCAD; Voltage Source Converter (VSC);
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Innovative Smart Grid Technologies - India (ISGT India), 2011 IEEE PES
  • Conference_Location
    Kollam, Kerala
  • Print_ISBN
    978-1-4673-0316-3
  • Type

    conf

  • DOI
    10.1109/ISET-India.2011.6145390
  • Filename
    6145390