DocumentCode
3240836
Title
An analysis of midpoint balance for the neutral-point-clamped three-level VSI
Author
Dong Ho Lee ; Lee, Seong R. ; Lee, Fred C.
Author_Institution
Bradley Dept. of Electr. Eng., Virginia Polytech. Inst. & State Univ., Blacksburg, VA, USA
Volume
1
fYear
1998
fDate
17-22 May 1998
Firstpage
193
Abstract
The three level voltage source inverter (VSI) is a good topology for high voltage and high power applications where no semiconductor devices are available. However, it has an inherent problem of midpoint charge balance. The problem becomes critical when the load is nonlinear and/or has large phase angle and harmonics. If it exceeds the critical points, there is no way to control the midpoint voltage by itself. The midpoint balancing problem is analyzed with respect to the reactive loads with harmonic currents and a way to solve the problem is suggested
Keywords
harmonics; invertors; voltage control; harmonic currents; harmonics; high power; high voltage; large phase angle; midpoint balance analysis; midpoint charge balance; midpoint voltage control; neutral-point-clamped three-level VSI; nonlinear load; reactive loads; three level voltage source inverter; Capacitors; Harmonic analysis; Instruments; Inverters; Phase distortion; Power semiconductor switches; Semiconductor devices; Stress; Topology; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics Specialists Conference, 1998. PESC 98 Record. 29th Annual IEEE
Conference_Location
Fukuoka
ISSN
0275-9306
Print_ISBN
0-7803-4489-8
Type
conf
DOI
10.1109/PESC.1998.701899
Filename
701899
Link To Document