  • Title

    The identification of internal and external faults for ±800kV UHVDC transmission line based on S-transform of the polarity wave

  • Author

    Shu, Hongchun ; Tian, Xincui ; Dai, Yuetao

  • Author_Institution
    Fac. of Electr. Eng., Kunming Univ. of Sci. & Technol., Kunming, China
  • Volume
    7
  • fYear
    2010
  • fDate
    16-18 Oct. 2010
  • Firstpage
    3060
  • Lastpage
    3063
  • Abstract
    There is a smoothing reactor and DC filter between the inverter and the direct current line to form a boundary in the HVDC transmission system. Since this boundary presents the stop-band characteristic to the high frequency transient voltage signals, the high-frequency transient voltage signal caused by external faults through boundary will be attenuated and the signals caused by internal faults will be unchanged. In this paper, a new technique in which the S-transform is used to analyze the transient signals is proposed for distinguishing internal faults from the external faults based on the significantly difference of high-frequency transient voltage on the point of protection.
  • Keywords
    HVDC power transmission; fault diagnosis; power filters; power transmission protection; transforms; DC filter; S-transform; UHVDC transmission line; direct current line; external fault identification; high frequency transient voltage signals; internal fault identification; inverter; polarity wave; smoothing reactor; voltage -800 kV; voltage 800 kV; Circuit faults; HVDC transmission; Inductors; Lightning; Smoothing methods; Transient analysis; S-transform; UHVDC transmission line; boundary unit; polarity — wave;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Image and Signal Processing (CISP), 2010 3rd International Congress on
  • Conference_Location
    Yantai
  • Print_ISBN
    978-1-4244-6513-2
  • Type

    conf

  • DOI
    10.1109/CISP.2010.5646181
  • Filename
    5646181