DocumentCode :
3247969
Title :
Performance of 20 kV Epoxy Resin Outdoor Insulator Under Various Environment Conditions
Author :
Latif, Melda ; Suwarno
Author_Institution :
Dept. of Electr. Eng., Andalas Univ., Padang
fYear :
2006
fDate :
38869
Firstpage :
353
Lastpage :
356
Abstract :
This paper explains the research results of leakage current and flashover measurement on epoxy resin 20 kV outdoor insulators in a chamber at various artificial polluted conditions. The waveform of the leakage current (LC) was measured using a digital storage oscilloscope. The digital data was transferred to a personal computer using a RS-232 cable. Further analysis of the waveform was done using Fast Fourier Transform. The result showed that LC was affected by various environment conditions like pollution, humidity and temperature. The flashover of insulators occurred at 64 kV for 2600 muS and 53 kV for 4300 muS in clean fog and high humidity condition
Keywords :
digital storage oscilloscopes; epoxy insulation; epoxy insulators; fast Fourier transforms; flashover; fog; humidity; insulator contamination; leakage currents; 24 kV; 64 kV; RS-232 cable; artificial polluted condition; digital data transfer; digital storage oscilloscope; epoxy resin outdoor insulator; fast Fourier transform; flashover measurement; fog condition; humidity condition; leakage current measurement; personal computer; temperature condition; Communication cables; Current measurement; Epoxy resins; Flashover; Humidity; Insulation; Leakage current; Microcomputers; Oscilloscopes; Pollution measurement; epoxy resin; flashover voltage; leakage current; outdoor insulator;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and applications of Dielectric Materials, 2006. 8th International Conference on
Conference_Location :
Bali
Print_ISBN :
1-4244-0189-5
Electronic_ISBN :
1-4244-0190-9
Type :
conf
DOI :
10.1109/ICPADM.2006.284188
Filename :
4062677
Link To Document :
بازگشت