DocumentCode
3249336
Title
Study on the On-line PD Measurement Technology for Power Transformer
Author
Kim, Kwang-Hwa ; Sun, Jong-Ho ; Yi, Sang-Hwa ; Han, Sang-Bo ; Kang, Dong-Sik
Author_Institution
Korea Electrotechnol. Res. Inst., Changwon
fYear
2006
fDate
38869
Firstpage
570
Lastpage
574
Abstract
Since partial discharges weaken the insulation performance of power transformers, the detection of PD is very important for prevention of fatal incidents. This study describes the use of electromagnetic coupler for the partial discharge measurement of transformers. Folded dipole antennas were used as sensors and installed in test chamber for experiments. The spectrum and oscillogram measured in various defect cells are analyzed and showed. And these partial discharges signals are measured at the same time by two types UHF amplifiers with different bandwidth and a conventional PD detector. From these results, decision of defect type is available
Keywords
UHF amplifiers; dipole antennas; electromagnetic coupling; partial discharge measurement; power transformer insulation; UHF amplifier; conventional PD detector; dipole antenna; electromagnetic coupler; insulation performance; oscillogram; partial discharge detection; partial discharge measurement; power transformer; Antenna measurements; Dipole antennas; Electromagnetic coupling; Electromagnetic measurements; Partial discharge measurement; Partial discharges; Power measurement; Power transformer insulation; Power transformers; UHF measurements;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and applications of Dielectric Materials, 2006. 8th International Conference on
Conference_Location
Bali
Print_ISBN
1-4244-0189-5
Electronic_ISBN
1-4244-0190-9
Type
conf
DOI
10.1109/ICPADM.2006.284242
Filename
4062731
Link To Document