DocumentCode :
3249410
Title :
Investigation of Contamination Flashover Voltage of A Porcelain Long Rod Insulator with Silicone Rubber Coating on The Trunks
Author :
Gautam, Basanta Kumar ; Matsumura, Shigeki ; Matsushita, Shouta ; Hashimoto, Takuma ; Sakanishi, Kenji ; Matsuoka, Ryosuke
Author_Institution :
Chubu Univ., Aichi
fYear :
2006
fDate :
38869
Firstpage :
591
Lastpage :
594
Abstract :
Higher flashover voltages of transmission line polymer insulators were found to be due to large ratio of shed to trunk diameter. This causes current density at the trunks to be very high and all the trunks get dried causing the applied voltage to the whole insulator divided and allotted to individual trunks. Similar effect was aimed by applying hydrophobic silicone rubber coating to the trunks of a porcelain long rod insulator. In this paper, investigation results of the contamination flashover voltages of porcelain long rod insulators coated with RTV silicone rubber coating on the trunks are presented
Keywords :
flashover; insulating coatings; insulator contamination; porcelain insulators; power transmission lines; silicone rubber; 293 to 298 K; RTV silicone rubber coating; contamination flashover voltage; current density; hydrophobic silicone rubber coating; porcelain long rod insulator; shed to trunk ratio diameter; transmission line polymer insulators; trunks; Coatings; Contamination; Current density; Flashover; Plastic insulation; Polymers; Porcelain; Rubber; Transmission lines; Voltage; Polymer insulator; RTV silicone rubber coating; contamination flashover voltage; hydrophobicity; porcelain long rod insulator;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and applications of Dielectric Materials, 2006. 8th International Conference on
Conference_Location :
Bali
Print_ISBN :
1-4244-0189-5
Electronic_ISBN :
1-4244-0190-9
Type :
conf
DOI :
10.1109/ICPADM.2006.284247
Filename :
4062736
Link To Document :
بازگشت