  • Abstract
    A new method for substation bus bar monitoring has been developed using a distributed data acquisition system and fiber optic communications. The advantages of this system include more accurate data sampling, ability to re-create the fault condition with the stored data in a simulation, a more secure transmission system with the use of fiber optics, and to prevent the false tripping of protection breakers. This new system involves current transformers, data acquisition models (DAM), and a data processing model. Each transmission line connected to the substation bus bar will have its own DAM that will sample the transmission lines three phase currents and voltages at the rate of 3,840 Hz. The samples will be converted to a 16-bit digital sample, and sent over a fiber optic network to a data processing module located in the control house. The fiber optic network will utilize a star topology and a custom designed protocol. The DAMs will be synchronized with a clocking signal sent from the data processing model. The data processing model will collect and process the sampled data to check for fault conditions on the bus bar. The data processor will then either trip the circuit breaker or sound an alarm, if a fault condition is detected
  • Keywords
    current transformers; data acquisition; optical fibre communication; power system measurement; power system protection; transformer substations; 16 bit; 3840 Hz; bus bar monitoring; clocking signal; current transformers; custom designed protocol; data acquisition models; data processing model; data sampling; distributed data acquisition system; fault condition; fiber optic communications; fiber optic network; protection breakers; secure transmission system; star topology; substation bus protection; Circuit faults; Current transformers; Data acquisition; Data processing; Optical fiber communication; Optical fiber networks; Optical fibers; Sampling methods; Substation protection; Transmission lines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Wescon/98
  • Conference_Location
    Anaheim, CA
  • ISSN
    1095-791X
  • Print_ISBN
    0-7803-5078-2
  • Type

    conf

  • DOI
    10.1109/WESCON.1998.716474
  • Filename
    716474