Polymeric insulation systems, subjected to high electrical stresses, are susceptible to localized degradation at stress enhancements caused by contaminants within the insulation or protrusions at electrode/insulation interfaces. The degradation is referred to as electrical treeing. This paper describes further studies in which the distributions, rather than the average values, of the various shape parameters as a function of aging are used
Keywords
XLPE insulation; ageing; cable insulation; partial discharges; trees (electrical); XLPE cable insulation; aging; contaminants; electrical treeing; electrical trees; electrode/insulation interfaces; high electrical stresses; localized degradation; partial discharge pulse characteristics; polymeric insulation systems; protrusions; shape parameters; stress enhancements; Aging; Dielectrics and electrical insulation; Electrodes; Partial discharges; Plastic insulation; Polymers; Shape; Stress; Thermal degradation; Trees - insulation;