• DocumentCode
    3255714
  • Title

    Breakdown strength of vegetable-based oils under AC and lightning impulse voltages

  • Author

    Vukovic, Dragana ; Tenbohlen, Stefan ; Harthun, Jörg ; Perrier, Christophe ; Fink, Harald

  • Author_Institution
    Inst. of Power Transm. & High Voltage Technol., Univ. Stuttgart, Stuttgart, Germany
  • fYear
    2011
  • fDate
    26-30 June 2011
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The breakdown strength of vegetable-based oil (VBO) and mineral oil is compared by means of experimental determination of breakdown voltage. These oils were tested under AC and positive lightning impulse voltages for uniform and non-uniform electrical field. The oil gap varied from 2 mm up to 85 mm. The results show same or higher AC breakdown strength of VBO compared to mineral oil for small gaps and uniform electrical field, whereas for lightning impulses and non-uniform field breakdown strength of VBO is reduced.
  • Keywords
    lightning protection; power transformers; transformer oil; vegetable oils; AC breakdown strength; breakdown voltage; electrical field; lightning impulse voltages; mineral oil; vegetable-based oils; Breakdown voltage; Electric breakdown; Electrodes; Minerals; Pollution measurement; Power transformers; Vegetable oils; Vegetable-based oil; breakdown voltage; mineral oil; power transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Dielectric Liquids (ICDL), 2011 IEEE International Conference on
  • Conference_Location
    Trondheim
  • ISSN
    2153-3725
  • Print_ISBN
    978-1-4244-7352-6
  • Electronic_ISBN
    2153-3725
  • Type

    conf

  • DOI
    10.1109/ICDL.2011.6015468
  • Filename
    6015468