DocumentCode
3255714
Title
Breakdown strength of vegetable-based oils under AC and lightning impulse voltages
Author
Vukovic, Dragana ; Tenbohlen, Stefan ; Harthun, Jörg ; Perrier, Christophe ; Fink, Harald
Author_Institution
Inst. of Power Transm. & High Voltage Technol., Univ. Stuttgart, Stuttgart, Germany
fYear
2011
fDate
26-30 June 2011
Firstpage
1
Lastpage
4
Abstract
The breakdown strength of vegetable-based oil (VBO) and mineral oil is compared by means of experimental determination of breakdown voltage. These oils were tested under AC and positive lightning impulse voltages for uniform and non-uniform electrical field. The oil gap varied from 2 mm up to 85 mm. The results show same or higher AC breakdown strength of VBO compared to mineral oil for small gaps and uniform electrical field, whereas for lightning impulses and non-uniform field breakdown strength of VBO is reduced.
Keywords
lightning protection; power transformers; transformer oil; vegetable oils; AC breakdown strength; breakdown voltage; electrical field; lightning impulse voltages; mineral oil; vegetable-based oils; Breakdown voltage; Electric breakdown; Electrodes; Minerals; Pollution measurement; Power transformers; Vegetable oils; Vegetable-based oil; breakdown voltage; mineral oil; power transformers;
fLanguage
English
Publisher
ieee
Conference_Titel
Dielectric Liquids (ICDL), 2011 IEEE International Conference on
Conference_Location
Trondheim
ISSN
2153-3725
Print_ISBN
978-1-4244-7352-6
Electronic_ISBN
2153-3725
Type
conf
DOI
10.1109/ICDL.2011.6015468
Filename
6015468
Link To Document