    The flashover voltage characteristic comparative analysis of the anti contaminant equipment

  • Author

    Park, Yong Up ; Kwon, Tae Ho ; Ra, Dong Chae

  • Author_Institution
    Korea Electr. Power Corp.(KEPCO), Daejeon
  • fYear
    2008
  • fDate
    7-11 Sept. 2008
  • Firstpage
    40
  • Lastpage
    43
  • Abstract
    We carried out the dry flashover test and wet flashover test, after the artificial contaminant damage work, in order to inspect the validness of the anti contaminant equipment as a suspension insulator (ceramic material, EPDM), LP insulator, arrester and COS. As a result of experiment, the dry flashover voltage value of the damaged equipment with the salinity was similar to the normal equipment even if the equipment is damaged with the salinity. But when the humidity was high under the damaged state, the flashover voltage value of some distribution equipment was low under the 20 kV.
  • Keywords
    arresters; distribution networks; flashover; insulator contamination; insulator testing; COS; LP insulator; anti contaminant equipment; arrester; artificial contaminant damage; comparative analysis; distribution equipment; dry flashover test; flashover voltage; suspension insulator; wet flashover test; Dielectrics and electrical insulation; Flashover; Frequency; Humidity; Insulator testing; Materials testing; Plastic insulation; Polymers; Porcelain; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 2008. (ISEIM 2008). International Symposium on
  • Conference_Location
    Mie
  • Print_ISBN
    978-4-88686-005-7
  • Electronic_ISBN
    978-4-88686-006-4
  • Type

    conf

  • DOI
    10.1109/ISEIM.2008.4664438
  • Filename
    4664438