The flashover voltage characteristic comparative analysis of the anti contaminant equipment
Author
Park, Yong Up ; Kwon, Tae Ho ; Ra, Dong Chae
Author_Institution
Korea Electr. Power Corp.(KEPCO), Daejeon
fYear
2008
fDate
7-11 Sept. 2008
Firstpage
40
Lastpage
43
Abstract
We carried out the dry flashover test and wet flashover test, after the artificial contaminant damage work, in order to inspect the validness of the anti contaminant equipment as a suspension insulator (ceramic material, EPDM), LP insulator, arrester and COS. As a result of experiment, the dry flashover voltage value of the damaged equipment with the salinity was similar to the normal equipment even if the equipment is damaged with the salinity. But when the humidity was high under the damaged state, the flashover voltage value of some distribution equipment was low under the 20 kV.
Keywords
arresters; distribution networks; flashover; insulator contamination; insulator testing; COS; LP insulator; anti contaminant equipment; arrester; artificial contaminant damage; comparative analysis; distribution equipment; dry flashover test; flashover voltage; suspension insulator; wet flashover test; Dielectrics and electrical insulation; Flashover; Frequency; Humidity; Insulator testing; Materials testing; Plastic insulation; Polymers; Porcelain; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulating Materials, 2008. (ISEIM 2008). International Symposium on
Conference_Location
Mie
Print_ISBN
978-4-88686-005-7
Electronic_ISBN
978-4-88686-006-4
Type
conf
DOI
10.1109/ISEIM.2008.4664438
Filename
4664438
Link To Document