DocumentCode
3257420
Title
Soft Transition Operation of UPS in High-Power-Factor Mode of Three-Phase Front-End Rectifier
Author
Dhomane, G.A. ; Suryawanshi, H.M.
Author_Institution
VNIT, Nagpur
fYear
2007
fDate
27-30 Nov. 2007
Firstpage
1431
Lastpage
1435
Abstract
A three-phase to single-phase ac-to-ac converter, with soft-transition of switches is presented. The converter has THD less than 4% and operates at almost unity-power-factor for wide variations in load, due to high frequency current injection, at the input of front-end- rectifier. A small filter is required at the output for filtering the high-frequency content. Sinusoidal PWM technique is used for controlling the output voltage. DSP is used for generating the desired gate pulses. The converter has high efficiency, low EMI emissions, high power packing density and suitable for UPS system. A Simulation and experimentation is carried out on a 3 kW converter and experimental results are in good agreement with simulation results.
Keywords
AC-AC power convertors; PWM rectifiers; digital signal processing chips; power factor; power filters; uninterruptible power supplies; voltage control; DSP; UPS soft transition operation; high frequency current injection; high power packing density; high-power-factor mode; single-phase AC-to-AC converter; sinusoidal PWM technique; three-phase front-end rectifier; voltage control; Digital signal processing; Filtering; Filters; Frequency conversion; Pulse width modulation; Rectifiers; Switches; Switching converters; Uninterruptible power systems; Voltage control; High-frequency-current-injection; High-power-factor; Power-factor-correction circuit; Soft-transition;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics and Drive Systems, 2007. PEDS '07. 7th International Conference on
Conference_Location
Bangkok
Print_ISBN
978-1-4244-0645-6
Electronic_ISBN
978-1-4244-0645-6
Type
conf
DOI
10.1109/PEDS.2007.4487892
Filename
4487892
Link To Document