Mitigation of power supply disturbance in electronic loads
Author
Basu, K.P. ; Nor, Normiza Mohd ; Hafidz, S.A.
Author_Institution
Fac. of Eng., Multimedia Univ., Cyberjaya, Malaysia
fYear
2011
fDate
28-30 Dec. 2011
Firstpage
1
Lastpage
5
Abstract
An alternate power supply guarantees the performance of loads during voltage disturbances in the normal supply. It is proposed to implement a quick change over of the power supply of single-phase electronic loads from the faulty phase to a healthy phase in a 3-phase system. Supercapacitors maintain the dc voltage during the period of disturbance. A zigzag transformer may also be used to rebuild a balanced 3-phase load voltage by isolating the faulty phase from the load. Both the 3-phase and single-phase loads may be supplied with the rated voltage during the period of disturbance. Use of a static transfer switch reduces the change over time to 0.02 second.
Keywords
electricity supply industry; power supply quality; supercapacitors; 3-phase load voltage; 3-phase loads; DC voltage; electronic loads; power supply disturbance mitigation; single-phase electronic loads; supercapacitors; time 0.02 s; voltage disturbances; voltage sags; zigzag transformer; Capacitors; Circuit faults; Impedance; Power supplies; Switches; Variable speed drives; Voltage fluctuations; Short-time power interruption; alternate power supply; power failure; super capacitor; voltage sag; zero sequence impedance; zigzag transformer;
fLanguage
English
Publisher
ieee
Conference_Titel
Energy, Automation, and Signal (ICEAS), 2011 International Conference on
Conference_Location
Bhubaneswar, Odisha
Print_ISBN
978-1-4673-0137-4
Type
conf
DOI
10.1109/ICEAS.2011.6147127
Filename
6147127
Link To Document