DocumentCode
3257859
Title
Determination of wind speed value in calculation of supply air volume
Author
Chen Ying
Author_Institution
Dept. of Fire Protection Eng., Chinese People´s Armed Police Force Acad., Langfang, China
fYear
2011
fDate
8-10 Aug. 2011
Firstpage
250
Lastpage
253
Abstract
Using the method of mechanical air supply can protect the escape route against smoke. The wind speed method is one of the most commonly used methods in determining the supply air volume. The average value of supply wind velocity v in the calculation parameters of wind speed method has been studied using numerical simulation method in this paper. The results show that at natural smoke venting, when the building is protected with sprinkler system, the value of v should take 0.7m/s, otherwise the value of v should take 0.9m/s.
Keywords
aerodynamics; numerical analysis; smoke; structural engineering; ventilation; wind; building escape route; mechanical air supply; natural smoke venting; smoke control; sprinkler system; supply air volume calculation; supply wind velocity; wind speed value determination; Atmospheric modeling; Buildings; Fires; Heating; Presses; Temperature distribution; Wind speed; FDS; mechanical pressurized air supply; numerical simulation; wind speed;
fLanguage
English
Publisher
ieee
Conference_Titel
Emergency Management and Management Sciences (ICEMMS), 2011 2nd IEEE International Conference on
Conference_Location
Beijing
Print_ISBN
978-1-4244-9665-5
Type
conf
DOI
10.1109/ICEMMS.2011.6015668
Filename
6015668
Link To Document