DocumentCode
3258175
Title
Evaluation of DTLR of power distribution line from sag measured using GPS
Author
Kamboj, S. ; Dahiya, R.
Author_Institution
Dept. of Electr. Eng., Nat. Inst. of Technol., Kurukshetra, India
fYear
2011
fDate
28-30 Dec. 2011
Firstpage
1
Lastpage
6
Abstract
Dynamic Thermal Line Rating (DTLR) is used to monitor and dynamically upgrade the existing power lines. The overhead conductor sag measurements using GPS has been used to evaluate DTLR in the present paper. GPS receiver BT359 has been used to measure overhead conductor sag of 440V power distribution line and DTLR has been determined at different air temperatures. The inherent error in raw altitude measurements obtained by GPS has been reduced using Least Square parameter estimation and wavelet analysis to obtain more accurate altitude measurements.
Keywords
Global Positioning System; height measurement; least squares approximations; overhead line mechanical characteristics; parameter estimation; power distribution lines; radio receivers; DTLR evaluation; GPS receiver BT359; air temperature; altitude measurement; dynamic thermal line rating evaluation; inherent error; least square parameter estimation; overhead conductor sag measurement; power distribution line; voltage 440 V; wavelet analysis; Conductors; Global Positioning System; Measurement uncertainty; Power measurement; Sea measurements; Temperature measurement; Transmission line measurements; DTLR; GUI; Least Square Parameter Estimation; Wavelet Analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Energy, Automation, and Signal (ICEAS), 2011 International Conference on
Conference_Location
Bhubaneswar, Odisha
Print_ISBN
978-1-4673-0137-4
Type
conf
DOI
10.1109/ICEAS.2011.6147154
Filename
6147154